3000A ELECTRICAL PRIMARY CURRENT INJECTION TEST SET- TEST-903

FEATURES

  • Portable designed
  • Quick and easy to use
  • With CT ratio test function
  • With 6m large current cable
  • Max current output up to 3300A
  • Built-in digital timer, resolution 1 ms
  • Built-in digital ammeter 0.5% accuracy
  • Permanent current up to 3000 A, 15KVA
  • Made up of two units, control and power unit
  • Thermal, short-circuit and overload protection
SKU: TEST-903 Category: Tag:

TEST-903 3000A primary current injection test kit adopts ARM chip to control the output process and large capacity of toroidal transformer. It is equipped with LCD screen display current meter, also showed primary current value, secondary current value, turn ratio and the action time. Aluminum alloy body with PC panel component the shell. TEST-903 primary current injection test kit is mainly applied to test CT turn ratio and polarity in the power system, the contact resistance, protection relay, low voltage & high voltage circuit breaker protection test and high voltage generator test etc, which need large current on-site or in the lab.

 

PARAMETERS

Electrical parameters
Accuracy ±0.5%
Power Supply (AC) 380V±10%·50A, 50Hz/60Hz
Current Output (AC) 3000A·5V or 1500A·10V
Capacity 15KVA
The current output waveform distortion ≤5%
Primary current
Range 0-3300A
Resolution 0.1A
Accuracy <0.5%
Secondary measurement
Range 0-6A
Resolution 0.001A
Accuracy <0.5%
Current duration
3000A range 3000A   2-3minutes 1500A   3-6minutes
1500A range 1500A   2-3minutes
Continuous output 1200A
With timer
Range 0.0001~999.999S
Resolution 0.001S
Accuracy <0.2% ±5 words
Standard
Standard IEC61010-1;IEC 61326-1
Communication port RS232
Cable length 6x6m, 95mm²
Mechanical parameters
Dimensions (W×D×H) (mm) 380×350×360 and 340×290×420
Weight(kg) Control Host 48kg, External voltage regulator weight 42kg
Environmental conditions
Operating Temperature -10°C to 50°C
Storage Temperature -40°C to 70°C
Relative humidity ≤95%,on-condensing

SELECTION GUIDE

Model Accuracy Primary Current Ammeter(0-6A) Timer Power Injection Current time Dimension(W×D×H) (mm) Weight Remark
TEST-901 0.5% 0-1100A YES YES 5KVA 1000A: 2-3min;
500A:3-6min
430×260×260 25KG Integrated structure
TEST-902 0.5% 0-2200A YES YES 12KVA 2000A:2-3min;
1000A:3-6min
360×300×295 and 320×300×300 35KG+15KG Fission structure
TEST-903 0.5% 0-3300A YES YES 15KVA 3000A: 2-3min;
1500A:3-6min
380×350×360 and 340×290×420 48KG+42KG Fission structure
TEST-905 0.5% 0-5500A YES YES 30KVA 5000A:2-3min;
2500A:3-6min
430×430×445 and 550×450×600 68KG+55KG Fission structure