TEST-901 1000A primary current injection test set

The GFUVE TEST-901 primary current injection test set uses ARM Chip to control the output for large capacity toroidal transformers. It is equipped with LCD display and current meter; it shows primary and secondary current value, turns ratio and the reaction time. The chassis is aluminium alloy body. TEST-901 is mainly applied to CT turn ratio testing in power systems and contact resistance tests which require high current.

SKU: TEST-901 Category: Tag:

 

Electrical parameters
Accuracy ±0.5%
Power Supply(AC) 220V±10%·25A, 50Hz/60Hz or
110V±10%·50A, 50Hz/60Hz
Current Output (AC) 1000A·5V or 500A·10V
Capacity 5KVA
The current output waveform distortion ≤5%
Dual protection overload electronic protection and software protection
Primary current
Range 0-1100A
Resolution 0.1A
Accuracy <0.5%
Secondary measurement
Range 0-6A
Resolution 0.001A
Accuracy <0.5%
Current duration
1000A range 1000A    2-3minutes
500A      3-6minutes
500A range 500A      2-3minutes
With timer
Range 0.0001~999.99S
Resolution 0.001S
Accuracy <0.5%±5 words
Mechanical parameters
Dimensions (W×D×H) (mm) 430×260×260
Weight(kg) 25
Environmental conditions
Temperature -10°C to 40°C
Relative humidity ≤80%